Integrity Testing

Introduction Products Insurance and Maintenence Halon Replacement
integrety testing BFPSA Under Construction Contact

 

 

 

 


Integrity Testing

It is vital to the effectiveness of a gaseous fire-fighting system that it is constantly maintained at peak performance. If in an emergency the system is called upon to discharge, it is of critical importance that the concentration of the gas, and the length of time it is retained in the room, are both at the originally specified level.

Your Legal Obligation


There was a time when full-discharge testing was the widely adopted method of assessing the effectiveness of gaseous installations. However, besides the unwelcome and wasteful effects of discharging large amounts of gasses – and particularly Halon 1301 – into the atmosphere, the test method was imprecise. Discharge testing techniques did not pinpoint the precise location of enclosure leakages; the test merely indicated a pass or fail status.

In addition to the growing pressure from insurance companies for organisations to adequately maintain their fire safety systems, building occupiers have other obligations. To ensure continued compliance with the relevant section of BS 5306, it is essential that all gaseous fire suppressant

installations – be they Halon 1301, NAF S-III, FM-200, CO2, Argonite or any of the other gasses currently on the market – are regularly maintained. An integral part of this maintenance activity is testing for leaks.

The Environmental Protection Act further reinforces this responsibility in the case of Halon installations. The Act demands that adequate safeguards are in place to avoid the accidental discharge of Halon – the manufacture of which was banned under the Montreal Protocol on the basis of its detrimental effect on the environment. It further requires that all installations are regularly tested for leaks by trained engineers.





 

Present standards of building design and construction have been shown by extensive research to be causing excessive leakage of cold outside air into our buildings. This results in winter heating loads that can be 50% greater than they need be.

 

 

 

Computer rooms, UPS rooms and control rooms are examples of the type of areas protected by gaseous extinguishant systems such as FM 200® and Inergen® . NFPA 2001 and ISO 14250 require that all new rooms must be integrity tested before acceptance and be subject to annual re-testing. 


 

 

 

 

Introduction Products Insurance and Maintenence Halon Replacement
integrety testing BFPSA Under Construction Contact

Top of This Page

 

Connect House, 21 Willow Lane, Mitcham, Surrey, CR4 4NA. Telephone 0208 288 1275